Datasheet

https://www.phoenixcontact.com/us/produkte/2788090
Nov 14, 20131/4
Surge protection device-TT-UKK5-D/ 24DC-2788090
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Double-level modular terminal block with suppressor diode as surge protection between both levels,
nominal voltage: 24 V DC, for mounting on NS 32 or NS 35/7.5, closed housing, terminal width: 6.2
mm, terminal height: 68 mm
Key commercial data
package_quantity
50
GTIN
4017918071332
Technical data
Dimensions
Height
68 mm
Width
6.2 mm
Length
80 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 85 °C
Degree of protection
IP20
General
Housing material
PA
Inflammability class according to UL 94
V2
Color
black
Standards for air and creepage distances
VDE 0110-1
Mounting type
DIN rail/G-profile rail
Design
Double-level terminal block
Direction of action
Line-Line
Protective circuit
IEC test classification
C3
VDE requirement class
C3
Nominal voltage U
N
24 V DC
Maximum continuous operating voltage U
C
28 V DC
Maximum continuous operating voltage U
C
20 V AC
Maximum continuous voltage UC (wire-wire)
28 V DC
Maximum continuous voltage UC (wire-wire)
20 V AC
Nominal current I
N
16 A