Datasheet

https://www.phoenixcontact.com/us/produkte/2810780
Nov 13, 20133/8
Signal conditioner-MINI MCR-SL-SHUNT-UI-NC-2810780
Technical data
Output data
Configurable/programmable
Yes, unconfigured
Voltage output signal
0 V ... 10 V
Voltage output signal
2 V ... 10 V
Voltage output signal
0 V ... 5 V
Voltage output signal
1 V ... 5 V
Voltage output signal
-10 V ... 10 V (The bi-polar output can be used only for bi-polar
input signals.)
Voltage output signal
-5 V ... 5 V (The bi-polar output can be used only for bi-polar input
signals.)
Current output signal
0 mA ... 20 mA
Current output signal
4 mA ... 20 mA
Max. output voltage
12.5 V
Max. output current
28 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
< 500 Ω (at 20 mA)
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC
Power consumption
< 450 mW (Current output)
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
12
Stripping length
12 mm
Screw thread
M3
Connection method
2-wire
General
Maximum transmission error
≤ 0.2 %
Maximum transmission error
< 0.4 % (Without adjustment)
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Limit frequency (3 dB)
(100 Hz / 30 Hz switchable)
Step response (10-90%)
3.5 ms (At 100 Hz)
Electrical isolation
Basic insulation according to EN 61010
Surge voltage category
II
Pollution degree
2
Rated insulation voltage
50 V AC/DC