Datasheet

https://www.phoenixcontact.com/us/produkte/2810939
Nov 14, 20132/5
Signal conditioner-MCR-C-UI-UI-DCI-NC-2810939
Technical data
Output data
Max. output current
30 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 500 Ω
Power supply
Supply voltage range
18 V DC ... 30 V DC
Max. current consumption
< 30 mA (without load)
Connection data
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
8 mm
Screw thread
M3
General
No. of channels
1
Maximum transmission error
≤ 0.1 % (of final value)
Maximum temperature coefficient
0.0075 %/K
Limit frequency (3 dB)
30 Hz
Alignment zero
± 2 %
Alignment span
± 2 %
Step response (10-90%)
11 ms
Protective circuit
Transient protection
Test voltage input/output
1.5 kV (50 Hz, 1 min.)
Test voltage power supply/signal
1 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2
Color
green
Housing material
Polyamide PA non-reinforced
Mounting position
Any
Conformance
CE-compliant
UL, USA / Canada
UL 508 Recognized
UL, USA / Canada
Class I, Div. 2, Groups A, B, C, D
GL
Germanischer Lloyd