Datasheet

© PHOENIX CONTACT 2010-07-01
104247_en_01
INTERFACE
MACX MCR-UI-UI-UP(-SP)(-NC)
Data sheet
1Description
MACX MCR-UI-UI 3-way isolating amplifiers are used to
electrically isolate and convert standard analog signals.
3-way isolation prevents interference between different
sensor circuits and thus improves the quality of the
measuring circuit.
DIP switches can be used to reconfigure the inputs and
outputs of the isolating amplifier, enabling more than 1600
signal conversions to be set.
When ordering preconfigured modules, specify the desired
input and output signal combination (see order key). If the
information is incorrect or unavailable, the devices will be
supplied with the standard configuration (0 ... 10 V input
signal, 0 ... 20 mA output signal).
Features
3-way electrical isolation
More than 1600 signal combinations can be set
using DIP switches (no software required)
Up to SIL 2 according to EN 61508 for the live zero
output
Installation in zone 2 permitted
Wide-range power supply including tolerance of
19.2...253VAC/DC
Step response (10 ... 90%) of 35 µs (at 10 kHz),
11 ms (at 30 Hz)
With screw or spring-cage connection
Active and passive output
WARNING: Explosion hazard
The device is designed for use in zone 2, if the specific conditions are observed.
Observe the safety regulations and installation notes on page 6.
When installing and operating the device, the applicable safety directives (including national safety directives),
accident prevention regulations, as well as general technical regulations, must be observed.
WARNING: Dangerous contact voltage
This work may only be carried out by qualified personnel who are familiar with the necessary safety precautions.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog
.
This data sheet is valid for all products listed on the following pages:
Configurable 3-way isolating amplifier with safe
isolation and wide-range power supply

Summary of content (15 pages)