Type 2 surge protection device-VAL-CP-2C-175-2859482
Technical data
Connection, protective circuit
Connection method
Biconnect terminal block
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
16 mm
Conductor cross section stranded min.
2.5 mm²
Conductor cross section stranded max.
16 mm²
Conductor cross section solid min.
2.5 mm²
Conductor cross section solid max.
25 mm²
Conductor cross section AWG/kcmil min.
12
Conductor cross section AWG/kcmil max
4
Remote indicator contact
Connection name
Remote fault indicator contact
Switching function
PDT contact
Connection method
Pluggable screw connection
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG/kcmil min.
28
Conductor cross section AWG/kcmil max
16
Maximum operating voltage U
max.
AC
250 V AC
Maximum operating voltage U
max
DC
125 V DC
Max. operating current I
max
1 A AC (inductive)
Max. operating current I
max
1 A AC (ohmic)
Max. operating current I
max
30 mA DC (inductive)
Max. operating current I
max
200 mA DC (ohmic)
Min. permissible switching capacity
0.12 VA (12 V, 10 mA)
Standards and Regulations
Standards/regulations
IEC 61643-1 1998
Standards/regulations
DIN EN 61643-11 2002
Standards/regulations
UL 1449
Standards/regulations
IEEE C62.1 / C62.34 / C62.45
classifications
eCl@ss
eCl@ss 4.0
27140201