Type 1/2 surge protection device-FLT-CP-2C-350-2859770
Technical data
General
Pollution degree
2
Mounting type
DIN rail: 35 mm
Design
DIN rail module, two-section, divisible
Number of positions
2
Message: Surge protection fault
Optical, remote indicator contact
Direction of action
2L-N/PE
Protective circuit
IEC test classification
I + II
IEC test classification
T1 + T2
EN type
T1 + T2
Lightning protection class
II /75 kA (TN-C)
Nominal voltage U
N
240 V AC (230/400 V AC ... 240/415 V AC)
Maximum continuous operating voltage U
C
(L-PEN)
350 V AC
U
T
(TOV-proof)
≤ 415 V AC (5 sec.)
Nominal frequency f
N
50 Hz (60 Hz)
Rated load current I
L
125 A (≤ 55°C)
Standby power consumption P
C
≤ 3.5 mW
Nominal discharge current I
n
(8/20) µs (L-PEN)
50 kA (all channels)
Impulse discharge current (10/350) µs, charge
25 As
Impulse discharge current (10/350) µs, specific energy
625.00 kJ/Ω
Impulse discharge current (10/350) µs, peak value l
imp
50 kA (2-pos.)
Impulse discharge current (10/350) µs, charge
12.5 As
Impulse discharge current (10/350) µs, specific energy
160.00 kJ/Ω
Impulse discharge current (10/350) µs, peak value l
imp
25 kA (1-pos.)
Voltage protection level U
P
(L-PEN)
≤ 1.5 kV
Residual voltage (L-PEN)
≤ 1.3 kV
Residual voltage (L-PEN)
≤ 1.1 kV (10 kA)
Residual voltage (L-PEN)
≤ 1 kV (5 kA)
Residual voltage (L-PEN)
≤ 1 kV (3 kA)
Response time (L-PEN)
≤ 25 ns
Max. required backup fuse with branch wiring
315 A (gL / gG)
Max. required backup fuse with V-type through wiring
125 A (gL / gG)
Recommended backup fuse maximum
160 A (gL/gG, 125 A with serial through wiring)
Short-circuit resistance I
P
with max. backup fuse (effective)
25 kA
Follow current quenching capacity If (L-PE)
25 kA (264 V AC)
Follow current quenching capacity If (L-PE)
3 kA (350 V AC)
Connection, protective circuit
Connection method
Screw terminal blocks
Connection type IN
Biconnect screw terminal block
Connection type OUT
Biconnect screw terminal block