Datasheet

https://www.phoenixcontact.com/gb/products/2861412
02/13/2018Page3/7
Inline terminal-IB IL AI 8/SF-PAC-2861412
Technical data
Analog inputs
Input name Analog inputs
Number of inputs 8
Connection method Inline shield connector
Connection technology 2-wire
Note regarding the connection technology shielded
A/D conversion time approx. 10 µs
Resolution A/D 16 bit
Limit frequency (3 dB) 3.5 kHz
Type of protection Surge protection, overcurrent protection
Data formats IB IL, IB ST, IB RT, standardized representation, PIO format
Measuring principle Successive approximation
Measured value resolution 16 bits (15 bits + sign bit)
Measured value representation 16 bit two's complement
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
0 mA ... 40 mA
-40 mA ... 40 mA
Input resistance current input 25 Ω (Shunt)
Voltage input signal 0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
0 V ... 25 V
-25 V ... 25 V
0 V ... 50 V
Input resistance of voltage input > 240 kΩ
Filtering 1st order low pass
Electrical isolation
Test section
7.5 V supply (bus logic), 24 V supply U
ANA
/ I/O 500 V AC 50 Hz 1 min.
7.5 V supply (bus logic), 24 V supply U
ANA
/functional earth ground 500 V
AC 50 Hz 1 min.
I/O / functional earth ground 500 V AC 50 Hz 1 min.
Standards and Regulations
Connection in acc. with standard CUL
Protection class III, IEC 61140, EN 61140, VDE 0140-1
Environmental Product Compliance
China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values