Datasheet

https://www.phoenixcontact.com/us/produkte/2862835
Nov 14, 20132/8
Inline terminal-IB IL 24 DI 32/HD-PAC-2862835
Technical data
General
Weight
185 g
Note on weight specifications
with male connectors
Mounting type
DIN rail
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
Test section
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
Test section
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
Test section
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Diagnostics messages
No None
Interfaces
Fieldbus system
Lokalbus
Name
Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Power supply for module electronics
Connection method
via potential routing
Supply voltage
24 V DC (via voltage jumper)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Ripple
5%
Supply current
max. 90 mA
Derating
No derating
Communications power U
L
7.5 V (via voltage jumper)
Current consumption
max. 90 mA (from the local bus)
Power consumption
max. 0.675 W (at U
L
)
Inline potentials
Communications power U
L
7.5 V DC
Current consumption from U
L
max. 90 mA
Main circuit supply U
M
24 V DC
Current consumption from U
M
max. 8 A DC
Segment supply voltage U
S
24 V DC (nominal value)
Current consumption from U
S
0 A DC
Digital inputs
Input name
Digital inputs
Connection method
Spring-cage connection
Connection method
1-wire
Number of inputs
32 (EN 61131-2 type 1)
Typical response time
2 ms
Protective circuit
Short-circuit and overload protection