Datasheet

https://www.phoenixcontact.com/us/produkte/2863915
Nov 14, 20131/8
Inline function terminal-IB IL TEMP 4/8 RTD-PAC-2863915
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Inline analog input terminal, complete with accessories (plug and labeling field), 8 channels, RTD
(resistance temperature detector), 2, 3-wire connection method
Product Description
This terminal block provides you with an inexpensive 8-channel input module for resistive temperature sensors.The module supports
platinum and nickel sensors in acc. with DIN and SAMA directives. With the platinum sensors, not only Pt 100, Pt 500 and Pt 1000 are
supported, but also the Pt 10000 (e.g. from building automation) and numerous other measuring sensors. The sensors are connected
using the 2 or 3-wire system.The measured temperature is displayed via 16-bit values per channel (2 x 4 channels in process data
multiplex) or via 16 bits per channel with PCP communication.Software library CD "CD AS SW LIB" contains function blocks and sample
programs for analog value processing.The Inline terminal can be identified using hinged labeling fields. The fields have insert cards
that can be labeled individually to suit the application. Zack marker strip ZBF 6... or Zack marker sheet ZBFM 6... can also be used for
labeling the terminal points. 
Product Features
Pt, Ni, Cu, KTY sensor types according to DIN and SAMA
Measured value acquisition with 16-bit resolution
Channel scout for optical channel identification
Connection of sensors in 2, 3, and 4-wire technology
Key commercial data
package_quantity
1
GTIN
4017918955410
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the
download area
Dimensions
Width
48.8 mm
Height
136.8 mm
Depth
71.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)