Datasheet

1Description
Standard signal -3-way isolating amplifier
MINI MCR-SL-I-I
© PHOENIX CONTACT
Data sheet
INTERFACE
MINI MCR-SL-I-I(-SP) standard signal 3-way isolating ampli-
fiers are used to electrically isolate, condition, amplify, and fil-
ter standard signals.
Electrically isolated 0...20 mA or 4...20 mA standard analog
signals are available on the input and output sides.
The power supply (19.2...30 V DC) can be supplied either via
connection terminal blocks "3"/"4" or "7"/"8" on the modules
or in conjunction with the DIN rail connector. Please refer to
the section titled "Power supply" for more information.
Features
3-way isolating amplifier
0...20!mA or 4...20!mA input and output signal range
Approval for Ex-zone 2 (nA)
Screw or spring-cage connection can be provided
Attention: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided
here during installation and observe the information in the "Safety regulations and installation notes".
Make sure you always use the latest documentation.
It can be downloaded from the product at www.phoenixcontact.net/catalog
.
This data sheet is valid for all products listed on the following page:
101946_en_03
2010-10-25