Datasheet

https://www.phoenixcontact.com/us/produkte/2865243
Nov 14, 20131/6
Repeater power supply-PI-EX-RPSS-2865243
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Ex-i analog input: Repeater power supply, HART. Feeds intrinsically safe 2-conductor measuring
transducers installed in an Ex area and transmits the 4-20 mA signal to a load in a safe area.
Galvanic 3-way isolation (input / output / supply).
Key commercial data
package_quantity
1
GTIN
4046356164290
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the
download area
Dimensions
Width
12.4 mm
Height
145 mm
Depth
147 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Permissible humidity (operation)
10 % ... 95 % (no condensation)
Degree of protection
IP20
Input data
Signal input
Intrinsically safe
Current input signal
4 mA ... 20 mA
Transmitter supply voltage
> 16 V (at 20 mA)
Transmitter supply voltage
> 15.3 V (at 22.5 mA)
Output data
Signal output
Current output
Current output signal
4 mA ... 20 mA (active)
Current output signal
4 mA ... 20 mA (14 ... 26 V ext. source voltage)