Datasheet

https://www.phoenixcontact.com/us/produkte/2866404
Nov 13, 20131/6
Power supply unit-TRIO-PS/ 3AC/24DC/40-2866404
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
DIN rail power supply unit, primary-switched mode, 3-phase, output: 24 V DC / 40 A
Product Description
TRIO POWER is the DIN-rail-mountable power supply unit with basic functions. With an output voltage of 5 V DC, 12 V DC, 24 V
DC, and 48 V DC and 1- and 3-phase versions with 60 W or 960 W, it is particularly suited for use in series production in mechanical
engineering. The wide-range input and international certification package allow worldwide implementation.The high MTBF of 500,000
h stands for high supply reliability. The devices can be connected in parallel to increase the capacity and redundancy.The clear LED
signaling and the device connection with double terminal block for plus and minus for fast potential distribution are further advantages of
this device series. A third minus terminal block simplifies the grounding on the secondary side. All power supply units are idle-proof and
short-circuit-proof and provide a regulated and adjustable output voltage. 
Product Features
Use the third negative terminal block as a grounding terminal block and minimize installation costs
Rugged design with metal housing and wide temperature range from -25 to +70°C
Maximum operational reliability thanks to high MTBF (mean time between failures) of more than 500,000 hours and high dielectric
strength of up to 300 V AC
Compensation of voltage drops by means of output voltage that can be adjusted on the front
Key commercial data
package_quantity
1
GTIN
4046356046688
Technical data
Dimensions
Width
139 mm
Height
130 mm
Depth
190 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 55° C derating)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
95 % (at 25 °C, no condensation)
Noise immunity
EN 61000-6-2:2005
Input data

Summary of content (6 pages)