Datasheet

TRIO-PS/3AC/24DC/5
103346_en_00 PHOENIX CONTACT 10
12 Input
Adjust
22.5-29.5V
DC OK
Output DC
24 V
5A
+
+
TRIO POWER
Input 2/3 AC
400-500 V
PE
(L3)
L2
L1
Protection of the primary side
The device must be installed in acc. with the regulations as in
EN 60950. It must be possible to disconnect the device using
a suitable isolating facility outside the power supply. Primary
circuit mains protection, for example, is suitable for this
purpose.
Required backup fuse (device and line protection)
External thermo-magnetic fuses are necessary for device
protection: 2/3 x 6 A, 10 A or 16 A power circuit breaker,
characteristic B (or identical function).
ATTENTION: Module can become
damaged
If an external fuse is triggered, there is most
probably a malfunction in the device. In this
case, the device must be inspected in the
factory!