Datasheet

TRIO-PS/3AC/24DC/5
103346_en_00 PHOENIX CONTACT 11
13 Output
Adjust
22.5-29.5V
DC OK
Output DC
24 V 5 A
+
+
TRIO POWER
Input 2/3 AC
400-500 V
PE
(L3)
L2
L1
+
Output DC
24 V 5 A
+
POWER
The connection is made using the "+" and "-" screw
connections on the screw connection of the DC output. At the
time of delivery, the output voltage is 24 V DC. The output
voltage can be set on the potentiometer.
Protection of the secondary side
The device is electronically protected against short circuit and
idling. In the event of a malfunction, the output voltage is
limited to 35 V DC.
ATTENTION: Module can become
damaged
Make sure that all output lines are dimensioned
according to the maximum output current or are
separately protected. The cables on the
secondary side must have sufficiently large
cross sections in order to keep the voltage
drops on the lines as low as possible.
You can fasten the connection cables to the
housing using cable binders.
Ensure that the cable binders and the
connection cables are designed for the surface
temperatures that occur in operation.
Make sure that the insulation of the connection
cables is not damaged when tightening the
cable binders.
14 Signaling
The "DC OK" LED enables evaluation of the function of the power supply directly on site.
State 1 State 2
"DC OK" LED ON OFF
Cause Output voltage > 21.5 V Output voltage < 21,5 V or no voltage at the output
Meaning Output voltage and output
current OK
The device is in operation, but there is a fault in the
consumer, the current consumption is greater than I
N
or the
output is short circuited.
The device is out of operation because there is no mains
voltage, the fuse on the primary side has been triggered, or
the device is faulty.