Datasheet

TRIO-PS/3AC/24DC/5
103346_en_00 PHOENIX CONTACT 3
Description Type Order No. Pcs.
Pkt.
Primary-switched power supply, 3-phase, output current 5 A TRIO-PS/3AC/24DC/5 2866462 1
Accessories Type Order No. Pcs.
Pkt.
Universal wall adapter UWA 182/52 2938235 1
Input data
Input nominal voltage range 2x / 3x 400 V AC ... 500 V AC
AC input voltage range 320 V AC ... 575 V AC (for 3-phase operation)
2x 360 V AC ... 575 V AC (for 2-phase operation)
AC frequency range 45 Hz ... 65 Hz
Current consumption Approx. 3x 0.3 A (400 V AC)
Approx. 3x 0.3 A (500 V AC)
2x 0.65 A (400 V AC)
2x 0.5 A (500 V AC)
Inrush current limitation < 15 A
I
2
t 0.2 A
2
s
Power failure bypass > 20 ms (400 V AC)
> 30 ms (480 V AC)
Typical response time < 1 s
Protective circuitry Transient surge protection Varistor
Recommended backup fuse for mains protection 2/3x 6 A (characteristic B)
2/3x 10 A (characteristic B)
2/3x 16 A (characteristic B)
Required backup fuse (device and line protection)
Discharge current to PE < 3.5 mA
Output data
Nominal output voltage 24 V DC ±1%
Setting range of the output voltage 22.5 V DC ... 29.5 V DC (> 24 V constant capacity)
Output current 5 A (-25°C ... 70°C)
Derating Above +55°C: 2.5% per Kelvin
Current limitation Approx 6 A (in the event of a short circuit)
Max. capacitive load Unlimited
Control deviation < 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Power loss nominal load max. 15 W
Maximum power dissipation idling 4 W
Efficiency > 89 %
Ascent time < 2 ms (U
OUT
(10% ... 90%))
Residual ripple < 30 mV
PP
Peak switching voltages < 30 mV
PP
Connection in parallel Yes, for redundancy and increased capacity
Connection in series No
Surge protection against internal surge voltages Yes, < 35 V DC
Resistance to reverse feed 35 V DC