Datasheet

https://www.phoenixcontact.com/gb/products/2866598
06/18/2019Page2/7
Uninterruptible power supply-MINI-DC-UPS/12DC/4-2866598
Technical data
Ambient conditions
Max. permissible relative humidity (operation) 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Input data
Nominal input voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC
Input voltage range DC 100 V DC ... 350 V DC (UL508: 100...250 V DC)
Buffer time
Can be set to: 0.5 min; 1 min; 2 min; 3 min; 5 min; 10 min; 15 min; 20
min; 30 min; permanent
Current consumption 0.65 A (230 V AC)
1.35 A (120 V AC)
Inrush current limiting/I²t
< 1.1 A
2
s
Mains buffering time see diagram
Typical response time 100 ms
Power factor (cos phi) approx. 0.5
Protective circuit Varistor
Input fuse, integrated 3.15 A (slow-blow, internal)
Output data
Nominal output voltage 12 V DC
Setting range of the output voltage (U
Set
)
10 V DC ... 16 V DC (AC input voltage available, AC input voltage not
available: Output voltage depending on the battery voltage: 13.6 V DC ...
9.6 V DC)
Nominal output current (I
N
)
4 A
Derating 60 °C ... 70 °C (2.5%/K)
Output current limit max. 7 A
Max. capacitive load unlimited
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Power loss nominal load max. 10.5 W
Maximum power dissipation in no-load condition 3.8 W
Power dissipation battery operation 2.9 W
Efficiency > 82 %
Residual ripple
< 50 mV
PP
Peak switching voltages nominal load
< 100 mV
PP
Connection in parallel No
Surge protection against internal surge voltages < 35 V DC
Feedback resistance 35 V DC
General
IQ technology no
Net weight 0.45 kg
Memory medium External, rechargeable battery 1.6 Ah / 2.6 Ah