Datasheet

https://www.phoenixcontact.com/ch/products/2866611
11/24/2016Page2/9
Uninterruptible power supply-TRIO-UPS/1AC/24DC/ 5-2866611
Technical data
Input data
Nominal input voltage range 100 V AC ... 240 V AC
AC input voltage range 85 V AC ... 264 V AC (Derating < 90 V AC: 2.5%V)
Input voltage range DC 100 V DC ... 350 V DC (UL508: 100 ... 250 V)
Buffer time
adjustable: 0.5 min; 1 min; 2 min; 3 min; 5 min; 10 min; 15 min; 20 min;
PC-Mode
Current consumption 1.1 A (230VAC, maximum)
1.8 A (120VAC, maximum)
Inrush current limiting/I²t
< 1.3 A
2
s
Power failure bypass see diagram
Typical response time 150 ms (230 V AC)
200 ms (120 V AC)
Power factor (cos phi) approx. 0.5
Protective circuit Transient surge protection Varistor
Input fuse, integrated 6.3 A (slow-blow, internal)
Output data
Nominal output voltage 24 V DC
Setting range of the output voltage (U
Set
)
22.5 V DC ... 29.5 V DC (Network operation; in the buffer mode,
dependent on the battery voltage of 27.9 V DC ... 19.2 V DC)
Nominal output current (I
N
)
5 A (-25°C ... 55°C)
Derating 55 °C ... 70 °C (2.5%/K)
Output current limit max. 6 A (Mains operation)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Efficiency > 88 % (230 V AC, network operation)
> 86 % (120 V AC, network operation)
> 86 % (Battery operation)
Residual ripple
< 10 mV
PP
Peak switching voltages nominal load
< 25 mV
PP
Connection in parallel Yes, 2
Surge protection against internal surge voltages Yes, < 35 V DC
Feedback resistance 35 V DC
General
IQ technology No
Net weight 1.1 kg
Memory medium External, battery 1.3 Ah / 3.4 Ah / 7.2 Ah / 12 Ah
Operating mode
Insulation voltage input/output 4 kV (type test)
2 kV (Routine test)
Protection class I
> 596000 h (40°C)
Mounting position horizontal DIN rail NS 35, EN 60715