User manual
STEP-UPS/24DC/24DC/3
PHOENIX CONTACT 6
Security
Degree of protection IP20
Protection class III
Input connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 12
Stripping length 6.5 mm
Screw thread M3
Tightening torque 0.6 Nm ... 0.8 Nm
Output connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 12
Stripping length 6.5 mm
Screw thread M3
Tightening torque 0.6 Nm ... 0.8 Nm
Signal connection data
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 12
Stripping length 6.5 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Ambient conditions
Ambient temperature (operation) 0 °C ... 40 °C
Ambient temperature (storage/transport) -20 °C ... 45 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, no condensation)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Shock 30 g in each direction, according to IEC 60068-2-27
Pollution degree in acc. with EN 50178 2
Climatic class 3K3 (in acc. with EN 60721)
Standards
Electrical safety (of information technology equipment) EN 60950-1/VDE 0805 (SELV)
Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV)
Approvals
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950
Current approvals can be found for the product in the download area.