Datasheet

https://www.phoenixcontact.com/us/produkte/2869912
Nov 14, 20132/5
Inline analog I/O terminal-IB IL EX-IS AIO 4/EF-PAC-2869912
Technical data
General
Weight
222 g
Mounting type
DIN rail
Interfaces
Fieldbus system
Lokalbus
Name
Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s
Power supply for module electronics
Power loss
4.7 W (per channel)
Analog inputs
Number of inputs
4
Connection method
Inline shield connector
Connection method
2, 3-wire
Input name
Analog inputs
Resolution A/D
16 bit (15 bit + sign bit)
Type of protection
Polarity protection, surge protection
Data formats
IB IL, standardized represention, S7 compatible
Current input signal
0 mA ... 20 mA
Current input signal
4 mA ... 20 mA
Voltage input signal
0 V DC ... 10 V DC
Voltage input signal
0 V ... 10 V
Current input signal
0 mA ... 20 mA
Current input signal
4 mA ... 20 mA
Analog outputs
Number of outputs
4 (Can be configured as input or output)
Connection method
Inline shield connector
Connection method
2-wire
Type of protection
Polarity protection, surge protection
Data formats
IB IL, standardized represention, S7 compatible
Current output signal
0 mA ... 20 mA
Current output signal
4 mA ... 20 mA
Load/output load current output
500 Ω
Inline potentials
Communications power U
L
5 V DC (via voltage jumper)
Current consumption from U
L
max. 50 mA
Safety data
Max. output voltage U
o
max. 28 V DC (output)
Max. output current I
o
max. 108 mA (output)
Max. output power P
o
max. 750 mW (output)