Datasheet

https://www.phoenixcontact.com/us/produkte/2885278
Nov 9, 20132/4
Monitoring relay-EMD-SL-3V-400-N-2885278
Technical data
Input data
Function
Window, with neutral conductor connection
Min. setting range
-30 % ... 20 % (From U
N
)
Max. setting range
-20 % ... 30 % (From U
N
)
Min setting range of the voltage threshold value
280 V AC ... 480 V AC
Max. setting range of the voltage threshold value
320 V AC ... 520 V AC
Setting range for response delay
0.2 s ... 10 s
Basic accuracy
± 5 % (of scale end value)
Setting accuracy
≤ 5 % (of scale end value)
Repeat accuracy
≤ 2 %
Voltage influence
≤ 0.5 %
Recovery time
500 ms
Contact side
Contact type
1 floating PDT
Maximum switching voltage
250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.
750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
Interrupting rating (ohmic load) max.
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse
5 A (fast-blow)
Power supply
Supply voltage range
24 V AC ... 230 V AC (see Power modules)
Supply voltage range
24 V DC (see Power modules)
General
Mechanical service life
Approx. 2 x 10
7
cycles
Operating mode
100% operating factor
Mounting position
Any
Assembly instructions
on standard DIN rail NS 35 in accordance with EN 60715
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Surge voltage category
III, basic insulation (as per EN 50178)
Housing insulation material
Polyamide PA, self-extinguishing
Color
green
Rated insulation voltage
300 V (According to EN 50178)
Conformance
CE-compliant
UL, USA / Canada
UL/C-UL listed UL 508
Connection data
Conductor cross section stranded min.
0.25 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section solid min.
0.5 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG/kcmil min.
20
Conductor cross section AWG/kcmil max
14