Datasheet

PLC-OPT- 24DC/ 48DC/100 Order No.: 2900352
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2900352
PHOENIX CONTACT Inc., USA Page 2 / 6
http://www.phoenixcon.com Mar 29, 2012
Switching threshold "1" signal in reference to U
N
≥ 0.8
Typical input current at U
N
8.5 mA
Typical response time 20 µs (at U
N
)
Typical turn-off time 300 µs (at U
N
)
Operating voltage display Yellow LED
Type of protection Protection against polarity reversal
Free-wheeling diode
Protective circuit/component Polarity protection diode
Damping diode
Transmission frequency 300 Hz
Output data
Output nominal voltage range 3 V DC ... 48 V DC
Limiting continuous current 100 mA
Voltage drop at max. limiting continuous current ≤ 1 V
Output circuit 2-wire, floating
Type of protection Protection against polarity reversal
Surge protection
Protective circuit/component Polarity protection diode
Connection data
Connection method Push-in connection
Stripping length 8 mm
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section stranded min. 0.14 mm²
Conductor cross section stranded max. 2.5 mm²
Conductor cross section AWG/kcmil min. 26
Conductor cross section AWG/kcmil max 14
General data
Width 6.2 mm
Height 80 mm
Depth 94 mm
Test voltage input/output 2.5 kV (50 Hz, 1 min.)
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -25 °C ... 70 °C