Datasheet

https://www.phoenixcontact.com/us/produkte/2900353
Nov 9, 20132/10
Solid-state relay module-PLC-OPT- 48DC/ 48DC/100-2900353
Technical data
Input data
Switching threshold "1" signal in reference to U
N
≥ 0.8
Typical input current at U
N
9 mA
Typical response time
30 µs (at U
N
)
Typical turn-off time
300 µs (at U
N
)
Operating voltage display
Yellow LED
Type of protection
Protection against polarity reversal
Type of protection
Free-wheeling diode
Protective circuit/component
Polarity protection diode
Protective circuit/component
Damping diode
Transmission frequency
300 Hz
Output data
Output voltage range
3 V DC ... 48 V DC
Limiting continuous current
100 mA
Voltage drop at max. limiting continuous current
≤ 1 V
Output circuit
2-wire, floating
Type of protection
Protection against polarity reversal
Type of protection
Surge protection
Protective circuit/component
Polarity protection diode
Connection data
Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
14
General
Test voltage input/output
2.5 kV (50 Hz, 1 min.)
Mounting position
Any
Assembly instructions
In rows with zero spacing
Operating mode
100% operating factor
Inflammability class according to UL 94
V0
Pollution degree
2
Surge voltage category
III
classifications
eCl@ss
eCl@ss 4.0
27371001