Datasheet

https://www.phoenixcontact.com/us/products/2900356
May 3, 20172/10
Solid-state relay module-PLC-OPT-230UC/ 48DC/100-2900356
Technical data
Input data
Input voltage range
207 V AC ... 253 V AC
Input voltage range
198 V DC ... 242 V DC
Switching threshold "0" signal in reference to U
N
≤ 0.3
Switching threshold "1" signal in reference to U
N
≥ 0.8
Typical input current at U
N
3.5 mA
Typical response time
3 ms (at U
N
)
Typical turn-off time
5 ms (at U
N
)
Type of protection
Bridge rectifier
Protective circuit/component
Bridge rectifier
Transmission frequency
10 Hz
Power dissipation for nominal condition
0.81 W
Output data
Output voltage range
3 V DC ... 48 V DC
Limiting continuous current
100 mA
Voltage drop at max. limiting continuous current
≤ 1 V
Output circuit
2-wire, floating
Type of protection
Reverse polarity protection
Type of protection
Surge protection
Protective circuit/component
Polarity protection diode
Connection data, input side
Connection name
Input side
Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section solid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
Connection data, output side
Connection name
Output side
Connection method
Push-in connection
Stripping length
8 mm
Conductor cross section solid
0.14 mm² ... 2.5 mm²
Conductor cross section flexible
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 14
General
Test voltage input/output
2.5 kV (50 Hz, 1 min.)
Mounting position
any
Assembly instructions
In rows with zero spacing
Operating mode
100% operating factor
Flammability rating according to UL 94
V0