6. Technical data
Type Order No. ELR H3-IES-SC- 24DC/500AC-0,6 2900566
ELR H3-IES-SC- 24DC/500AC-2 2900567
ELR H3-IES-SC- 24DC/500AC-9 2900569
ELR H3-IES-SC-230AC/500AC-0,6 2900689
ELR H3-IES-SC-230AC/500AC-2 2900568
ELR H3-IES-SC-230AC/500AC-9 2900570
Input data ELR...-24DC/... ELR...-230AC/...
Rated control supply voltage U
s
as per IEC 60947-1 / UL 508
24 V DC 230 V AC (50/60 Hz)
Control supply voltage range 19.2 ... 30 V DC
(32 V DC, max. 1 min.)
85 ... 253 V AC
Control supply voltage Switching level "Safe off" < 5 V DC < 5 V AC
Rated control supply current as per IEC 60947-1 40 mA 4 mA
Control input ON:
Switching level "Low" -3 ... 9.6 V DC < 44 V AC
Switching level "Safe off" < 5 V DC < 5 V AC
Switching level "High" 19.2 ... 30 V DC 85 ... 253 V AC
Input current 5 mA 7 mA
Output data load side ELR...-0.6 ELR...-2 ELR...-9
Circuit principle Safety end level with bypass, three-phase
electrically isolated switch-off
Rated operating voltage U
e
as per IEC 60947-1 500 V AC (50/60 Hz)
Operating voltage range as per IEC 60947-1
as per UL 508
42...550 V AC
42...500 V AC
Load current at 20°C (see 8.2. Derating curve) 0.075...0.6 A 0.18...2.4 A 1.2... 9.0 A
Load current at 20°C without safety function and
asymmetry recognition (see 8.2. Derating curve)
0... 0.6 A 0...2.4 A 0...9.0 A
Rated operating current I
e
as per IEC 60947-1
AC-51 as per IEC 60947-4-3
AC-53a as per IEC 60947-4-2
as per UL 508
0.6 A
0.6 A
0.6 A
2.4 A
2.4 A
2.4 A
9 A
6.5 A
6.5 A
Nominal switching performance as per UL 508
Full Load (power factor = 0.4)
Full Load (power factor = 0.8)
0.3 kW (0.4 HP)
0.5 kW (0.6 HP)
0.9 kW (1.2 HP)
1.7 kW (2.2 HP)
2.3 kW (3.0 HP)
4.6 kW (6.1 HP)
Leakage current (input, output) 0 mA 0 mA 0 mA
Residual voltage at I
e
< 300 mV < 300 mV < 500 mV
Surge current 100 A (t = 10 ms)
Input protective circuit Varistors
Short circuit current rating SCCR acc. to UL 508 - suitable for use on a circuit capable of delive-
ring not more than 5 kA
rms
symmetrical amperes,
500 V maximum
- suitable for use on a circuit capable of delive-
ring not more than 100 kA
rms
symmetrical am-
peres, 500 V maximum when protected by a
30 A class J or CC fuse