Hybrid motor starter-ELR H5-I-SC-230AC/500AC-9-2900578
Technical data
Input data
Rated actuating current I
C
7 mA
Switching threshold "0" signal, voltage
44 V AC
Switching threshold "1" signal voltage
85 V AC
Protective circuit
Surge protection
Typical response time
< 35 ms
Typical turn-off time
< 80 ms
Operating voltage display
Green LED
Status display
Yellow LED
Indication
Red LED
Input name
Control input right/left
Output data
Output name
AC output
Nominal output voltage
500 V AC
Nominal output voltage range
42 V AC ... 550 V AC
Load current
max. 9 A (see derating curve)
Rated operating current at AC-51
9 A
Rated operating current at AC-53a
6.5 A
Leakage current
0 mA
Residual voltage
< 0.5 V
Surge current
100 A (t = 10 ms)
Type of protection
Surge protection
Output name
Acknowledge output
Note
Confirmation 01: Floating PDT contact
Nominal output voltage
max. 250 V AC
Continuous load current
6 A
Output data, signaling contact
Measuring via
Current transformer for line current on L1 and L3
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
26
Conductor cross section AWG/kcmil max
14
General
Test voltage input/output
4 kV
rms
Mounting position
Vertical (horizontal DIN rail)
Assembly instructions
Can be aligned with spacing = 20 mm