Datasheet

https://www.phoenixcontact.com/us/produkte/2901416
Nov 9, 20131/5
Safety relays-PSR-SCP-42-48UC/ESAM4/3X1/1X2B-2901416
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
The figure shows 48 V AC/DC
Safety relay for emergency stop and safety door monitoring up to SIL 3 or Cat. 4, PL e according to
EN ISO 13849, single or two-channel operation, 3 enabling current paths, nominal input voltage of
42 ... 48 V AC/DC, plug-in screw terminal blocks.
Product Features
Up to Cat. 4/PLe according to ISO13849-1, SILCL3 according to IEC62061, SIL3 according to IEC61508
Manually monitored and automatic activation in a single device
Basic insulation
Single and two-channel control
3 enabling current paths, 1 signaling current path
Key commercial data
package_quantity
1
GTIN
4046356591997
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the
download area
Dimensions
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
75 %
Max. permissible humidity (storage/transport)
75 %
Input data
Input voltage range
42 V AC/DC ... 48 V AC/DC
Input voltage range in reference to U
N
0.85 ... 1.1
Typical input current at U
N
95 mA