Datasheet

https://www.phoenixcontact.com/gb/products/2901997
01/16/2018Page2/9
Loop-powered isolators-MINI MCR-2-2I-2I-ILP-PT-2901997
Technical data
Input data
Number of inputs 2
Configurable/programmable no
Current input signal 0 mA ... 20 mA
4 mA ... 20 mA
Response current approx. 200 µA
Input voltage limitation 30 V
Voltage dissipation 3.1 V (I = 20 mA)
Output data
Output name Current output
Number of outputs 2
Configurable/programmable no
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output < 600 Ω (at I = 20 mA output signal)
Transmission Behavior 1:1 to input signal
Power supply
Supply voltage range 9.6 V DC ... 30 V DC (no separate supply voltage necessary)
Power consumption 600 mW
Connection data
Connection method Push-in connection
Single conductor/terminal point, solid, with ferrule, min. 0.14 mm²
Single conductor/terminal point, solid, with ferrule, max. 2.5 mm²
Single conductor/terminal point, solid, without ferrule, min. 0.14 mm²
Single conductor/terminal point, solid, without ferrule, max. 2.5 mm²
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 2.5 mm²
Min. AWG conductor cross section, flexible 24
Max. AWG conductor cross section, flexible 12
Stripping length 10 mm
General
No. of channels 2
Maximum transmission error ≤ 0.1 % (of final value)
Maximum temperature coefficient ≤ 0.002 %/K (of measured value / 100 Ω load)
Additional error, load-dependent < 0.075 % (of measured value / 100 Ω load)
Limit frequency (3 dB) 100 Hz
Electrical isolation Reinforced insulation in accordance with IEC 61010-1
Overvoltage category II
Degree of pollution 2
Rated insulation voltage 300 V (effective)