Datasheet

UNO-PS/1AC/24DC/ 90W/C2LPS
105950_en_00 PHOENIX CONTACT 4
4 Technical data
Input data
Nominal input voltage 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
AC frequency range 45 Hz ... 65 Hz
Current consumption 1.5 A (120 V AC)
1 A (230 V AC)
Inrush current limitation < 40 A (typical)
I
2
t < 1.5 A
2
s
Typical response time < 1 s
Power failure bypass > 25 ms (120 V AC)
> 100 ms (230 V AC)
Protective circuit Transient surge protection Varistor
Input fuse, integrated 3.15 A (slow-blow, internal)
Choice of suitable fuses 6 A ... 16 A (Characteristics B, C, D, K)
Input connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 14
Stripping length 8 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Output data
Nominal output voltage 24 V DC ±1%
Output current 3.75 A (-25°C ... 55°C)
Derating 55 °C ... 70 °C (2.5%/K)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Ascent time < 0.5 s (U
OUT
(10 % ... 90 %))
Residual ripple < 45 mV
PP
(with nominal values)
Connection in parallel No
Connection in series No
Protection against surge voltage on the output 35 V DC
Resistance to reverse feed 35 V DC
Output connection data
Connection method Screw connection
Conductor cross section, solid 0.2 mm² ... 2.5 mm²
Conductor cross section, stranded 0.2 mm² ... 2.5 mm²
Conductor cross section AWG/kcmil 24 ... 14
Stripping length 8 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm