UNO-PS/1AC/12DC/100W Primary-switched power supply unit Data sheet 105987_en_00 1 © PHOENIX CONTACT 2014-03-14 Description The UNO POWER power supply unit impresses in worldwide use thanks to maximum energy efficiency. Low noload losses and the high degree of efficiency save energy. Features Thanks to its high power density, the UNO POWER power supply unit is the ideal solution, particularly in compact control boxes. – – – – Worldwide use thanks to input voltage range of 85 V AC ...
UNO-PS/1AC/12DC/100W 2 Table of contents 1 Description .............................................................................................................................. 1 2 Table of contents ..................................................................................................................... 2 3 Ordering data .......................................................................................................................... 3 4 Technical data ....................
UNO-PS/1AC/12DC/100W 3 Ordering data Description Type Order No. Pcs. / Pkt. Primary-switched UNO power supply for DIN rail mounting, input: singlephase, output: 12 V DC/100 W UNO-PS/1AC/12DC/100W 2902997 1 Accessories Type Order No. Pcs. / Pkt. Redundancy module, 5 V ... 24 V DC, 2 x 10 A, 1 x 20 A. UNO-DIODE/5-24DC/2X10/1X20 2905489 1 Our range of accessories is being continually extended, our current range can be found in the download area.
UNO-PS/1AC/12DC/100W 4 Technical data Input data Nominal input voltage 100 V AC ... 240 V AC Input voltage range 85 V AC ... 264 V AC AC frequency range 45 Hz ... 65 Hz Current consumption 1.7 A (120 V AC) 1 A (230 V AC) Inrush current limitation < 30 A (typical) I2t < 1.
UNO-PS/1AC/12DC/100W Power consumption Efficiency > 89.5 % Maximum power dissipation NO-Load < 0.4 W Power loss nominal load max. < 12 W General data Insulation voltage input/output 4 kV AC (type test) 3 kV AC (routine test) MTBF > 500000 h (According to EN 29500) Housing material polycarbonate Foot latch material Plastic POM Dimensions W / H / D 55 mm / 90 mm / 84 mm Weight 0.
UNO-PS/1AC/12DC/100W Conformance with EMC Directive 2004/108/EC Noise immunity according to EN 61000-6-2 EN 61000-6-2 requirement Tested Electrostatic discharge EN 61000-4-2 Housing contact discharge 4 kV (Test intensity 2) 6 kV (Test intensity 3) Housing air discharge 8 kV (Test intensity 3) 8 kV (Test intensity 3) Comments Criterion B Criterion B Electromagnetic HF field EN 61000-4-3 Frequency range 80 MHz ... 1 GHz Test field strength 10 V/m Frequency range 1.4 GHz ...
UNO-PS/1AC/12DC/100W 5 Intended use This power supply unit features IP20 protection and is intended for installation in housing. It is suitable for use in industrial applications. 6 Structure 6.1 Device elements 6.2 Block diagram 2 3 + + – – L N Element Meaning Fuse 4 Decoupling 1 Bild 1 1. 2. 3. 4.
UNO-PS/1AC/12DC/100W 7 Assembly 7.1 Unpacking Before mounting the power supply unit, it must be checked for damage: – Take the device out of its packaging. – Check the device for any damage sustained during transport. – Retain the package slip for future use. – Dispose of packaging in an environmentally-friendly way. 7.2 Mounting the power supply unit The power supply unit is intended for installation in a distributor box or control cabinet. The power supply unit is designed for convection cooling.
UNO-PS/1AC/12DC/100W 150 75 30 Please note the following before mounting the power supply unit: – The minimum distance from other devices that must be observed in order to ensure convection cooling is: 30 mm vertically, 0 mm horizontally – The device dimensions 90 55 27 58 63 90 84 70 41 35 105987_en_00 5 PHOENIX CONTACT 9
UNO-PS/1AC/12DC/100W 7.3 Mounting on a DIN rail The power supply unit can be installed on all 35 mm DIN rails according to EN 60175. A Bild 3 7.4 B Mounting on a DIN rail Normal mounting position When installed, the input terminal blocks must be at the bottom and the output terminal blocks at the top. If the power supply unit is installed in a mounting position other than the normal mounting position, the output power must be reduced.
UNO-PS/1AC/12DC/100W 8 Installing the power supply unit 8.1 Safety regulations and installation notes WARNING: risk of electric shock! Only qualified specialist personnel may install, start up, and operate the device. Observe the national safety and accident prevention regulations. 8.2 The device can be connected to single-phase AC or threephase power grids (TN-S, TN-C, TT, and IT) while considering the nominal input voltage.
UNO-PS/1AC/12DC/100W 8.3 Device connections 8.4 Connecting cables Screw connection for input AC L/N Bild 6 Use copper cables with an operating temperature > 75°C (ambient temperature < 55°C) and > 90°C (ambient temperature < 75°C). Screw connection for input AC L/N Screw connection for output DC +/- Bild 8 1. Bild 7 Screw connection for output DC +/- 2. Connecting cables Connect the supply lines to the input AC L/N connection terminal blocks.
UNO-PS/1AC/12DC/100W 9 Operating behavior of the power supply unit 9.1 Normal operation In normal operation, the loads are supplied with a constant output voltage of 12 V DC. 9.2 Overload response [V] In the event of overload (I > IN), the device reduces its output voltage. If the output voltage is greater than UN x 0.9, the green DC OK LED lights up. If the output voltage drops below UN x 0.5, the device shuts down. After a short time, the device attempts to start up again.
UNO-PS/1AC/12DC/100W 9.4 Behavior in the case of alternative mounting positions For mounting positions that differ from the normal mounting position, the output power must be reduced (position-dependent derating). The characteristic curve can be used to determine the maximum output power to be drawn for each ambient temperature for different mounting positions.
UNO-PS/1AC/12DC/100W [%] Rotated mounting position 180° X-axis 110 100 90 80 70 60 50 40 30 20 0 -25 0 10 20 30 40 50 60 70 80 [°C] Y Z X [%] Rotated mounting position 270° X-axis 110 100 90 80 70 60 50 40 30 20 0 -25 0 10 20 30 40 50 60 70 80 [°C] Y Z X 105987_en_00 PHOENIX CONTACT 15
UNO-PS/1AC/12DC/100W [%] Rotated mounting position 90° Z-axis 110 100 90 80 70 60 50 40 30 20 0 -25 0 10 20 30 40 50 60 70 80 [°C] Y Z X [%] Rotated mounting position 270° Z-axis 110 100 90 80 70 60 50 40 30 20 0 -25 0 10 20 30 40 50 60 70 80 [°C] Y Z X 105987_en_00 PHOENIX CONTACT 16
UNO-PS/1AC/12DC/100W 10 Operating the power supply unit 10.1 Function monitoring DC OK LED The DC OK LED is available for visual function monitoring of the power supply unit. DC OK LED Meaning State description Remedy 105987_en_00 Status 1 Lit Output voltage > 10.5 V Status 2 OFF Output voltage < 10.
UNO-PS/1AC/12DC/100W 10.2 Operating power supply units in parallel Power supply units of the same type can be connected in parallel to increase both redundancy and power. To ensure symmetrical current distribution, all cable connections from the power supply unit to the busbar must be the same length and have the same conductor cross section. Redundant operation Redundant circuits are suitable for supplying systems which place particularly high demands on operational safety.
UNO-PS/1AC/12DC/100W 10.3 Operating the power supply unit in series Two devices can be connected in series to double the voltage. Only power supply units of the same type should be connected in series. Series connection should always be used when the output voltage of the module is not sufficient. For example, devices with 24 V DC nominal output voltage each supply 48 V DC in series.