Datasheet

https://www.phoenixcontact.com/gb/products/2904605
04/10/2019Page4/7
Power supply unit-QUINT4-PS/1AC/12DC/2.5/PT-2904605
Technical data
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz ... 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1 GHz ... 6 GHz
Test field strength 3 V/m (Test Level 2)
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN61000-4-6
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V (Test Level 3)
Conducted noise emission EN 55016 EN61000-6-4 (Class A)
Standards/regulations EN 61000-4-8
EN 61000-4-11
EN 61000-4-9
EN 61000-4-12
EN 61000-4-16
EN 61000-4-18
Standard - Safety of transformers EN 61558-2-16
Standard - Electrical safety IEC61010-2-201(SELV)
Standard – Safety extra-low voltage IEC61010-1 (SELV)
IEC61010-2-201 (PELV)
Standard - Safe isolation IEC61558-2-16
IEC 61010-2-201
Standard – Limitation of mains harmonic currents EN61000-3-2
UL approvals UL Listed UL 61010-1
UL Listed UL 61010-2-201
UL 1310 Class 2 Power Units
ANSI/UL121201 Class I, Division 2, Groups A, B, C, D (Hazardous
Location)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15Hz, ±2.5mm amplitude; 15Hz ... 100Hz: 2.3g 90Min. (in
accordance with IEC 60068-2-6)
Overvoltage category (EN 61010-1) II(≤5000m)
Overvoltage category (EN 62477-1) III(≤2000m)
Drawings