Datasheet

https://www.phoenixcontact.com/gb/products/2904611
08/07/2018Page3/9
Power supply unit-QUINT4-PS/1AC/48DC/10-2904611
Technical data
Output data
Protection against surge voltage on the output ≤ 60VDC
Control deviation < 0.5 % (Static load change 10% ... 90%)
< 2 % (Dynamic load change 10% ... 90%, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple
< 70 mV
PP
(with nominal values)
Output power 480 W
Typical response time 300 ms (from SLEEP MODE)
Maximum power dissipation in no-load condition < 5 W (120 V AC)
< 5 W (230 V AC)
Power loss nominal load max. < 36 W (120 V AC)
< 28 W (230 V AC)
General
Net weight 1.3 kg
Efficiency typ. 94 % (120 V AC)
typ. 95 % (230 V AC)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2.4 kV AC (routine test)
Insulation voltage output / PE 0.5 kV DC (type test)
0.5 kV DC (routine test)
Protection class I
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 1100000 h (25 °C)
> 676000 h (40 °C)
> 317000 h (60 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: P
N
≥50%, 5mm horizontally, 15mm next to active
components, 50mm vertically
alignable: P
N
<50%, 0mm horizontally, 40mm vertically top, 20 mm
vertically bottom
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 30
Conductor cross section AWG max. 10
Stripping length 8 mm