Datasheet

1Description
Power supply unit
QUINT4-PS/3AC/24DC/5
© PHOENIX CONTACT
Data sheet
QUINT POWER power supplies with integrated NFC
interface and SFB technology ensure superior system
availability.
Adaptable
Signaling thresholds and characteristic curves can be
set via NFC
Powerful
SFB technology: 6 times the nominal current for 15ms
Power reserves:
Static boost of up to 125%(P
N
) for a sustained period
Dynamic boost of up to 200%(P
N
) for 5s
Preventive
Comprehensive signaling
Robust
–Mains buffering > 20ms
High degree of immunity, thanks to integrated gas-filled
surge arrester (6kV)
Technical data (short form)
Input voltage range 3x 400 V AC ... 500 V AC
-20 % ... +10 %
2x 400 V AC ... 500 V AC
-10 % ... +10 %
Mains buffering 28 ms (3x 400 V AC)
40 ms (3x 480 V AC)
Nominal output voltage (U
N
) 24 V DC
Setting range of the output voltage
(U
Set
)
24 V DC ... 29.5 V DC
Residual ripple < 30 mV
PP
Nominal output current (I
N
)
Static Boost (I
Stat.Boost
)
Dynamic Boost (I
Dyn.Boost
)
Selective Fuse Breaking (I
SFB
)
5 A
6.25 A
10 A (5 s)
30 A (15 ms)
Output power (P
N
)
Output power (P
Stat. Boost
)
Output power (P
Dyn. Boost
)
120 W
150 W
240 W
Efficiency typ. 89 % (400 V AC)
typ. 87.5 % (480 V AC)
MTBF (IEC 61709, SN 29500) > 914000 h (40°C)
Ambient temperature (operation) -25 °C ... 70 °C
-40°C (startup type tested)
> 60 °C Derating: 2,5 %/K
Dimensions W/H/D 36 mm / 130 mm / 125 mm
Weight 0.6 kg
All technical specifications are nominal values and refer to a room temperature of 25 °C and 70 % relative
humidity at 100 m above sea level.
107103_en_00
2016-08-18