1Description
SIL3 coupling relay for safety-related switch on
PSR-PC50
© PHOENIX CONTACT
Data sheet
The PSR-PC50 SIL coupling relay can be used for power
adaptation and electrical isolation in Safe-State-ON applica-
tions up to SIL3 according to IEC61508 as well as
IEC61511.
By filtering the controller test pulses, premature failure of the
safety relays is prevented.
The contact side is fully monitored for open circuit and short
circuit as well as load and diagnostics supply voltage.
If an error occurs, the internal device input impedance is af-
fected. As such, the test pulses sent from the controller are
disrupted and the error is reported to the corresponding dig-
ital output without additional wiring effort.
Features
–SIL3 coupling relays for safety-related switch on
Applications: Energized-to-Safe
Complete monitoring of the load side for:
- Open circuit
- Short circuit
- Presence of supply voltage for diagnostics and loads
Error message output through interrupting test pulses of
the higher-level controller
Easy proof test
Integrated DCS test pulse filter
Low inrush current
One undelayed enabling channel
Optional plug-in screw or spring-cage terminal blocks
Special design for avoiding spurious trips
Housing width 17.5 mm
Compatible with EMERSON DeltaV SIS SLS1508 and
CSLS (further controller cards on request)
WARNING: Risk of electric shock
Observe the safety instructions in the corresponding section!
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This data sheet is valid for all products listed on the following pages.
105818_en_01
2014-08-18