Datasheet

PSR-MS60
106171_en_01 PHOENIX CONTACT 3
Description Type Order No. Pcs. / Pkt.
Safety relay for emergency stop, safety doors, and light grids up to SIL3,
SILCL3, Cat.4, PLe, 2-channel operation, automatic start, 2 enabling cur-
rent paths (1-channel), U
S
=24VDC, fixed screw terminal block
PSR-MS60-2NO-24DC-SC 2904958 1
3Ordering data
4 Technical data
Hardware/firmware version
HW/FW 00/-- (The technical data and safety characteristics are valid as of the specified
HW/FW version.)
Input data
Rated control supply voltage U
S
24 V DC -15 % / +10 %
Rated control supply current I
S
typ. 40 mA
Typical inrush current 4.5 A (t=120s at U
s
)
< 20 mA (with U
s
/I
x
to S12)
< 20 mA (with U
s
/I
x
to S22)
Current consumption < 5 mA (with U
s
/I
x
to S12)
< 5 mA (with U
s
/I
x
to S22)
Power consumption at U
S
typ. 0.96 W
Voltage at input/start and feedback circuit 24 V DC -15 % / +10 %
Filter time 1 ms (at A1 in the event of voltage dips at U
s
)
max. 1.5 ms (Test pulse duration)
min. 7.5 ms (Test pulse rate)
Test pulse rate=5xTest pulse width
Max. permissible overall conductor resistance
(Input and reset circuit at U
S
)
150
Typical response time at U
s
< 175 ms
Typical starting time with U
s
< 250 ms (when controlled via A1)
Typical release time with U
s
< 20 ms (when controlled via A1 or S12 and S22.)
Recovery time < 500 ms
Maximum switching frequency 0.5 Hz
Operating voltage display 1 x green LED
Status display 2 x green LEDs
Protective circuit Surge protection Suppressor diode
Reverse polarity protection for rated control supply voltage
Output data
Contact type 2 enabling current paths
Contact material AgSnO
2
Minimum switching voltage 10 V AC/DC
Maximum switching voltage 250 V AC/DC
Limiting continuous current 6 A (N/O contact)
Maximum inrush current 6 A
Inrush current, minimum 3 mA
Sq. Total current 72 A
2
(see to derating)
Switching capacity min. 30 mW
Mechanical service life 10 x 10
6
cycles
Output fuse 6 A gL/gG (N/O contact)
4 A gL/gG (for low-demand applications)