Datasheet

https://www.phoenixcontact.com/gb/products/2905007
06/18/2019Page3/7
DC/DC converters-QUINT-PS/12DC/12DC/8-2905007
Technical data
Output data
Power loss nominal load max. 11.8 W
General
Net weight 0.8 kg
Efficiency > 89 %
Insulation voltage input/output 1.5 kV (type test)
1 kV (routine test)
Protection class III
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 1614000 h (25°C)
> 920000 h (40°C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: P
N
≥50%, 5mm horizontally, 15mm next to active
components, 50mm vertically
alignable: P
N
<50%, 0mm horizontally, 40mm vertically top, 20 mm
vertically bottom
Connection data, input
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 8 mm
Screw thread M3
Connection data, output
Connection method Pluggable screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Connection data for signaling
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²