Datasheet

https://www.phoenixcontact.com/us/products/2906060
May 3, 20171/7
Hybrid motor starter-ELR H5-IES-PT-24DC/500AC-9-T-2906060
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
The figure shows the ELR H5-
IES-PT- 24DC/500AC-9 version
Hybrid motor starter for reversing 3~AC motors up to 550VAC, with 24VDC input, 9A output
current, emergency stop function, adjustable overload shutdown, higher transient voltage strength,
and push-in connection.
Your advantages
22.5 mm wide
Safety level according to IEC 61508-1: SIL 3, ISO 13849: PL e
Reduction in wiring
Space saving
Long service life
3-phase loop bridges
Adjustable current for bimetal function
Low-wear switching
Key commercial data
package_quantity
1
GTIN
4055626024592
Technical data
Device supply
Rated control circuit supply voltage U
S
24 V DC
Control supply voltage range
19.2 V DC ... 30 V DC
Rated control supply current I
S
40 mA
Type of protection
Surge protection
Type of protection
Reverse polarity protection
Input data
Input name
Control input right/left
Rated actuating voltage U
C
24 V DC
Triggering voltage range
19.2 V DC ... 30 V DC
Rated actuating current I
C
5 mA
Switching threshold
9.6 V (“0” signal)
Switching threshold
19.2 V (“1” signal)
Switching level
< 5 V DC (For EMERGENCY STOP)
Typical turn-off time
< 30 ms