Datasheet

https://www.phoenixcontact.com/gb/products/2907161
06/18/2019Page2/7
Uninterruptible power supply-TRIO-UPS-2G/1AC/24DC/10-2907161
Technical data
Dimensions
Depth with alternative assembly 68 mm
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Max. permissible relative humidity (operation) ≤ 93 % (At +25°C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height ≤ 4000 m (> 2000 m, observe derating)
Input data
AC input voltage range 100 V AC ... 240 V AC -15 % ... +10 %
Inrush current limiting/I²t
< 0.2 A
2
s
Mains buffering time ≥ 25 ms (120 V AC)
Typical response time 200 ms
Input fuse, integrated 6.3 A (slow-blow, internal)
Output data
Nominal output voltage 24 V DC
Setting range of the output voltage (U
Set
)
24 V DC ... 28 V DC (> 24V constant capacity)
Nominal output current (I
N
)
10 A
Dynamic Boost (I
Dyn.Boost
)
15 A
Derating
> 60 °C (2.5%/K of P
Out
nom.)
Control deviation < 0.55 % (Static load change 10% ... 90%)
Maximum power dissipation in no-load condition < 3 W (230 V AC)
Efficiency typ. 90 % (120 V AC)
typ. 91 % (230 V AC)
typ. 96 % (Battery operation)
Residual ripple < 20 mV
Connection in parallel yes, with diode module uncoupled
Surge protection against internal surge voltages < 30 V DC
Feedback resistance ≤ 35 V DC
General
Net weight 1.34 kg
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Protection class I
MTBF (IEC 61709, SN 29500) > 2007013 h (230 V AC, at 25 °C)
> 1210518 h (230 V AC, at 40 °C)
> 575978 h (230 V AC, at 60 °C)