Datasheet

https://www.phoenixcontact.com/gb/products/2907753
06/18/2019Page3/7
Redundancy module, with protective coating-QUINT4-S-
ORING/12-24DC/1X40/+-2907753
Technical data
General
alignable: P
N
<50%, 0mm horizontally, 40mm vertically top, 20 mm
vertically bottom
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section flexible min. 0.5 mm²
Conductor cross section flexible max. 16 mm²
Conductor cross section AWG min. 20
Conductor cross section AWG max. 6
Stripping length 10 mm
Screw thread M4
Connection data, output
Connection method Screw connection
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 16 mm²
Conductor cross section flexible min. 0.5 mm²
Conductor cross section flexible max. 16 mm²
Conductor cross section AWG min. 20
Conductor cross section AWG max. 6
Stripping length 10 mm
Screw thread M4
Connection data for signaling
Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise emission Additional basic standard EN 61000-6-5 (immunity in power station)
Noise immunity
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2
(industrial), and EN 61000-6-5 (power station equipment zone )
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)