5.2.3 Step 3: Configuration of the current input (current trans-
former)
Configuring the current input is the third step of the basic device configuration.
Figure 5-15 Current input, current transformer
Primary Enter the primary current of the application here.
Secondary Select the secondary current (1 A or 5 A) of the current transformer.
Invert With this function, the respective phase of the current transformer is inverted by the firm-
ware. It is no longer necessary to rewire the two conductors.
Depending on the device selection and the associated device-specific current sensors,
the current input setting may vary.