User Manual

EMpro - multifunctional energy measuring devices for DIN rail mounting
144 / 196
PHOENIX CONTACT 109357_en_00
Figure 11-8 Modbus settings
Please observe the following:
Each slave is assigned an address between 1 and 247.
Each address is used only once.
There is only one master per RS-485 network.
All devices use the same parameters for the baud rate, stop bits and parity.
You can configure the following parameters that are supported by the RS-485 interface:
Baud rates: 2400, 4800, 9600, 19200, 38400, 57600 and 115200 bps
Stop bits: 1, 2
Parity: even, odd, none
The parameters can also be set via Modbus/TCP.