User Manual

EMpro - multifunctional energy measuring devices for DIN rail mounting
174 / 196
PHOENIX CONTACT 109357_en_00
R/W: Read and write
It is possible to both read and write to this register.
W: Write only
This register can only be written. Attempting read access to this register causes an error.
W/R0: Write only and read 0
This register can only be written. Read access to this register results in a zero as response.
Data type
This column contains the data type to be used for decoding the contents of each respective
register.
ASCII
Each register (16 Bit) contains two ASCII characters. When the number is entered, the
number of individual registers contained in the character string is determined.
Example:
Dec:1234567
Hex: 0X31, 0X32, 0X33, 0X34, 0X35, 0X36, 0X37
Zero-terminated: “12345670”
Hex: 0X31, 0X32, 0X33, 0X34, 0X35, 0X36, 0X37, 0X00
Number of registers = 4: Hex: 0X3231, 0X3433, 0X3534, 0X0037
Bit mask
Each bit (bit 15-bit 0) of the register (16 bit) is evaluated individually.
Example: “Resetting the tariff meter”
Bit 0: Reset tariff 1
Bit 1: Reset tariff 2
Bit 2: Reset tariff 3
Bit 3: Reset tariff 4
An individual tariff meter, or any combination of meters from all tariff meters can be reset.
Bool
This data type makes a logical statement.
0: false
1: true
Fl32
IEEE-754-single number 1.8.23 (32 bits, two 16-bit registers):
1 sign bit: positive and negative
8 exponent bits: value range of 38 decimal places