User Manual

Technical data
109357_en_00 PHOENIX CONTACT 179 / 196
Signal OFF time 30 ms
Digital output in accordance with 61131-2 (type 3)
Nominal voltage 24 V DC
Rated output current Ie 0.1 A
Output voltage range 19.2 V DC ... 30 V DC
Output current range 0 mA ... 100 mA
Ethernet interface
RJ45/LAN 100Base-TX
Display
Type LCD display, two-color, backlit
Refresh 1 s, adjustable
Electrical isolation
Basic insulation: housing against all potentials
Overvoltage category III at 300 V AC
Overvoltage category II at 600 V AC
IEC 61010-1
Reinforced insulation: supply against all other potentials
Overvoltage category III at 300 V AC
Overvoltage category II at 600 V AC
IEC 61010-1
Reinforced insulation: voltage measurement input against
all other potentials
Measurement category III at 300 V AC
Measurement category II at 600 V AC
IEC 61010-1
Test voltage 4 kV AC (50 Hz, 1 min.)
Functional insulation: current measurement input against all
other potentials
Functional insulation: digital I/Os
Functional insulation: communication interface
Pollution degree 2
Ambient conditions
Ambient temperature (operation) -10°C...+55°C
Ambient temperature (storage/transport) -25°C…+85°C
Permissible humidity (operation) 95% non-condensing
Altitude 2,000 m
Connection data
Conductor cross section, current (rigid/flexible) 0.2 mm² ... 4 mm² / 0.2 mm² ... 6 mm²
Conductor cross section, voltage (rigid/flexible) 0.5 mm² ... 2.5 mm² / 0.5 mm² ... 4 mm²
Conductor cross section, supply (rigid/flexible) 0.14 mm² ... 2.5 mm²
Conductor cross section, digital I/O (rigid/flexible) 0.14 mm² ... 1.5 mm² / 0.14 mm² ... 2.5 mm²
Conductor cross section, communication (rigid/flexible) 0.14 mm² ... 2.5 mm²
Technical data [...]