EMpro - multi-functional energy measuring devices for front panel installation
110 / 192
PHOENIX CONTACT 108904_en_00
Settings Set the alarm according to your requirements.
Figure 10-18 Menu: “Settings, Alarm”
Confirm with digital input You can use the checkbox to define that manual acknowledgment of an alarm is required.
The acknowledgment is performed via the digital input, which has to be configured for this
purpose.
Identifier) The identifier can be used to assign a user-specific designation to the alarms.
Alarm 1…4 You can use the four tabs to define the alarm configuration for each alarm.
Data source Select the measurement value to be monitored.
High limit and low limit Use the checkbox to select the monitoring function. Depending on which function you se-
lected, enter the value to be monitored.
Delay Enter the tripping delay for the alarm in seconds.
Hysteresis For the switching threshold, a hysteresis in percent is required. Enter it here.