User Manual

Functions
108904_en_00 PHOENIX CONTACT 127 / 192
Figure 10-33 “Menu: Logging, Settings”
Log 1...8 Here, you can configure up to eight different logging parameters.
Data source Select the desired electrical parameter for the logging from the drop-down menu.
Interval Enter the interval time in minutes. The shortest duration that can be set is 1 minute.
The maximum logging duration depends on the configured interval. For an interval of 15
minutes, the logging capacity is approx. 90 days. If you shorten the interval, the logging ca-
pacity is also reduced (e.g., 10 minute interval/60 days logging capacity).
Circular buffer Activate the circular buffer if you want to use the FIFO principle (first-in/first-out) for the data
logging.
Deactivate the circular buffer if you want to define a fixed starting point.
The logging automatically stops once the memory is full.