Technical data
108904_en_00 PHOENIX CONTACT 175 / 192
Supply
Supply voltage range 80 V AC ... 480 V AC
120 V AC ... 300 V DC
Nominal supply voltage 100 V AC ... 400 V AC +/-20%
150 V DC ... 250 V DC +/-20%
Frequency AC sine (50/60 Hz)
Power consumption <4 W
Digital input in accordance with 61131-2 (type 3)
Nominal voltage 24 V DC
Nominal current -
Input voltage range 0 V DC ... 30 V DC
Signal ON time 30 ms
Signal OFF time 30 ms
Digital output in accordance with 61131-2 (type 3)
Nominal voltage 24 V DC
Rated output current I_e 0.1 A
Output voltage range 19.2 V DC ... 30 V DC
Output current range 0 mA ...100 mA
Ethernet interface
RJ45/LAN 100Base-TX
Display
Type LCD display, two-color, backlit
Refresh 1 s, adjustable
Electrical isolation
Basic insulation: housing against all potentials
Overvoltage category III at 300 V AC
Overvoltage category II at 600 V AC
IEC 61010-1
Reinforced insulation: supply against all other potentials
Overvoltage category III at 300 V AC
Overvoltage category II at 600 V AC
IEC 61010-1
Reinforced insulation: voltage measurement input against
all other potentials
Measurement category III at 300 V AC
Measurement category II at 600 V AC
IEC 61010-1
Test voltage 4 kV AC (50 Hz, 1 min.)
Functional insulation: current measurement input against all
other potentials
Functional insulation: digital I/Os
Functional insulation: communication interface
Pollution degree 2
Technical data [...]