3.2 Installation
DANGER: Risk of electric shock
If the device is disconnected, the secondary side of the relevant current transformers
must be short circuited.
Install the current sensors and corresponding measuring devices only when the power
supply of the system is disconnected.
When the current transformer is operated with an open secondary circuit, hazardous volt-
ages may occur at the secondary terminal blocks.
When measuring by means of current transformers or Rogowski coils, the accuracy is
greatly influenced by the quality of the current sensors used.