User Manual

Communication
109357_en_00 PHOENIX CONTACT 147 / 196
11.3 PROFINET
11.3.1 Software
1. Check whether the firmware of your energy measuring device is up to date with the
firmware available on the Phoenix Contact homepage. If the firmware is not up to date,
download the current firmware from the specific product site at
phoenixcontact.com
(see Section “Firmware update” on page 131).
2. Download the current GSDML file for your energy measuring device from the Phoenix
Contact website.
Additional requirements:
Pertinent knowledge of the preferred PROFINET engineering system
Executable project with configured controller
11.3.2 Preparing the GSDML file
1. Unpack the ZIP file on your file system.
11.3.3 Integrating the GSDML file
Integrate the GSDML file into your existing engineering system.
An example of the integration is shown below, using the TIA portal V15.
1. Select “Options, Manage general station description files (GSD)”.
Figure 11-9 “Options, Manage general station description files (GSD)”