Datasheet

https://www.phoenixcontact.com/us/produkte/2964005
Nov 10, 20132/9
Extension module-PSR-SPP- 24UC/URM4/5X1/2X2-2964005
Technical data
Output data
Contact type
1 confirmation current path
Contact material
AgSnO
2
, + 0.2 µm Au
Maximum switching voltage
250 V AC/DC
Minimum switching voltage
15 V AC/DC
Limiting continuous current
6 A (N/O contact)
Limiting continuous current
3 A (N/C contact 11/12)
Maximum inrush current
6 A
Maximum inrush current
3 A (N/C contact 11/12)
Inrush current, minimum
25 mA
Sq. Total current
72 A
2
(I
TH
2
= I
1
2
+ I
2
2
+ ... + I
5
2
)
Interrupting rating (ohmic load) max.
144 W (24 V DC, τ = 0 ms, N/C contact 11/12: 72 W)
Interrupting rating (ohmic load) max.
288 W (48 V DC, τ = 0 ms, N/C contact 11/12: 144 W)
Interrupting rating (ohmic load) max.
110 W (110 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.
88 W (220 V DC, τ = 0 ms)
Interrupting rating (ohmic load) max.
1500 VA (250 V AC, τ = 0 ms, N/C contact 11/12: 750 VA)
Maximum interrupting rating (inductive load)
42 W (24 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
42 W (48 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
42 W (110 V DC, τ = 40 ms)
Maximum interrupting rating (inductive load)
42 W (220 V DC, τ = 40 ms)
Switching capacity min.
0.4 W
Output fuse
6 A fast blow
Output fuse
C6 (24 V AC/DC) automatic device
General
Relay type
Electromechanically forcibly guided, dust-proof relay.
Mechanical service life
Approx. 10
7
cycles
Mounting position
Any
Category according to EN 13849-1
4
Stop category
0
Name
Air and creepage distances between the power circuits
Standards/regulations
DIN EN 50178/VDE 0160
Rated surge voltage / insulation
4 kV / Basic isolation, (safe isolation, reinforced insulation and
6 kV between input circuit and enabling current paths(43/44,
53/54, 63/64, 71/72) and between 43/44, 53/54, 63/64, 71/72
themselves.)
Rated insulation voltage
250 V
Pollution degree
2
Surge voltage category
III
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section stranded min.
0.2 mm²