Datasheet

Technical data
Dimensions Width Length Height NS 35/7,5
[mm] 18 81 65.5 18 81 65.5
Max. electrical data I
max.
[A] U
max.
[V] Max. Ø [mm²] AWG (UL)
32
2
) 690
2
) 1.5 - 25 18-3 30
IEC 60947-1/-3
Rated data IEC UL CSA IEC/
EN60079-7
Rated voltage [V] 690
2
) 600 600 - 600
Nominal current / cross section [A] / [mm²] 32
2
) / 16 30 / - 30 / - - 32
Rated cross section [mm²] 16 - - - 25 - - -
Cross section range AWG 16 - 4 18-3 18-3 - 16 - 4 - 18-4 -
Connection capacity Solid Stranded Ferrule
without/with plastic sleeve
1 conductor [mm²] 1.5 - 25 1.5 - 16 1.5 - 16 1.5 - 16 1.5 - 25 1.5 - 25 1.5 - 16 1.5 - 16
2 conductors (of the same type) [mm²] 1.5 - 4 1.5 - 4 1.5 - 4 - 1.5 - 4 1.5 - 4 1.5 - 4 -
2 stranded conductors with a TWIN ferrule [mm²] - - - 1.5 - 10 - - - 1.5 - 10
Max. cross section with insertion bridge [mm²] 10 10 - - 10 10 - -
General data
Fuse type / dimensions – / [mm] Midget / 10.3 x 38
Stripping length [mm] 12
Screw thread M5
Tightening torque [Nm] 2.5 - 3
Insulating material PA
Inflammability class according to UL 94 V0
Ordering data
Description
No. of
pos.
Color Type I
max
Order No.
Pcs. /
Pkt.
Fuse terminal block, for mounting on NS35..., for
10.3x38mm midget
fuseinserts,690VAC/440VDC
black UK 10,3-HESI N 3048386 10
With LED display
1
) black UK 10,3-HESILED N 690 3048399 10
Fuse terminal block, for mounting on NS35..., for
fuse inserts CLASS CC 10.3 x 38 mm
black
black
Accessories
Insertion bridge, can be separated, insulated spine
1-phase 2 gray EB 2-18 76 A 3009300 50
1-phase 3 gray EB 3-18 76 A 3009305 50
1-phase 56 gray EB 56-18 76 A 3009299 5
3-phase 56 gray EB 56-18/L1-L2-L3 76 A 3009367 5
Partition plate, 2mm wide gray TPN-UK 3003062 10
Connection pin, for connecting several fuse
terminal blocks, 2-pos.
black VS-UK 10,3-HESI N 2POL 3048532 10
3-pos. black VS-UK 10,3-HESI N 3POL 3048409 10
Screwdriver SF-SL 0,6X3,5-100 S-VDE 1212587 10
Center groove marking ZBF 10 (see Catalog 5)
402
PHOENIX CONTACT
UKK ...-HESI lever-type fuse terminal
blocks
Notes:
For detailed information on applications and power dissipation
data, see phoenixcontact.net/products
1
) If the fuse is faulty, the downstream circuit is not off load.
2
) The current and voltage are determined by the fuse.
The UK...-HESI fuse terminal blocks are
used to accommodate fuse inserts that
are mainly used in the USA
56-pos. insertion bridges and insertion
bridges for three phases are available
LED display indicates that a fuse has
blown
When selecting and using cartridge fuse
terminal blocks and inserts, IEC60127-6/
DINEN 60127-6 should be adhered to
Terminal blocks
UK universal terminal blocks
16 (25) mm², 32 A, lever-type fuse terminal
block for 10.3 x 38 mm midget fuses