Datasheet

Technical data
Dimensions Width Length Height NS 35/7,5
[mm] 8.2 72.5 56.5 10.2 79 60.5
Dimensions Width Length Height NS 32
[mm] 8.2 72.5 61.5 10.2 79 65.5
Max. electrical data I
max.
[A] U
max.
[V] Max. Ø [mm²] AWG (UL)
6.3
2
) 500
2
) 0.2 - 4 26-10 10
IEC 60947-7-3
Rated data IEC UL CSA IEC/
EN60079-7
Rated voltage [V] 500
2
) 600 600 - 500
Nominal current / cross section [A] / [mm²] 6.3
2
) / 1 12 / - 6.3 / - - 10
Rated cross section [mm²] 4 - - - 16 - - -
Cross section range AWG 24 - 12 26-10 28-10 - 20 - 6 26-8 26-8 -
Connection capacity Solid Stranded Ferrule
without/with plastic sleeve
1 conductor [mm²] 0.2 - 4 0.2 - 4 0.25 - 4 0.25 - 4 0.5 - 16 0.5 - 16 0.5 - 10 0.5 - 10
2 conductors (of the same type) [mm²] 0.2 - 1.5 0.2 - 1.5 0.25 - 1.5 - 0.5 - 4 0.5 - 4 0.5 - 4 -
2 stranded conductors with a TWIN ferrule [mm²] - - - 0.5 - 1.5 - - - 0.5 - 6
Max. cross section with insertion bridge [mm²] 4 4 - - 10 10 - -
General data
Fuse type / dimensions – / [mm] G / 5 x 20 / 5 x 25 / 5 x 30 G / 6,3 x 32
Stripping length [mm] 8
Screw thread M3
Tightening torque [Nm] 0.5 - 0.8
Insulating material PA
Inflammability class according to UL 94 V0
Ordering data
Description
No. of
pos.
Color Type I
max
Order No.
Pcs. /
Pkt.
Fuse terminal block, for mounting on NS32... or
NS35..., for cartridge fuse inserts 5 x 20, 5 x 25
and 5 x 30 mm
black UK 5-HESI 3004100 50
With LED display for 12-30 V AC/DC black UK 5-HESILED 24 3004126 50
With LED display for 110-250 V AC/DC
1
) black UK 5-HESILA 250 3004142 50
Fuse terminal block, for mounting on NS 32... or
NS35..., for cartridge fuse inserts 6.3 x 32 mm.
black
With LED display for 12-30 V AC/DC
1
) black
With LED display for 110-250 V AC/DC
1
) black
Accessories
Insertion bridge, can be separated, fully insulated
2 gray EBS 2- 8 32 A 3118151 100
3 gray EBS 3- 8 32 A 3118148 50
10 gray EBS 10- 8 32 A 3118135 10
Connection pin, for coupling several fuse terminal
blocks, made of plastic, 1 m long
gray VS 3004207 1
Screwdriver SF-SL 0,6X3,5-100 S-VDE 1212587 10
Lateral groove marking ZB 8 (see Catalog 5)
Lever marking
394
PHOENIX CONTACT
Lever-type fuse terminal blocks
UKK...–HESI
Notes:
For further technical notes on power dissipation, refer to page 616.
1
) If the fuse is faulty, the downstream circuit is not off load.
2
) The current is determined by the fuse used, the voltage by the
LED display. Observe max. power dissipation.
Safety lever locked in end position
Large area for marking
For 5mm and 6.3mm cartridge fuse
inserts
Versions with LED display
Terminal blocks
UK universal terminal blocks
4 (4) mm², 6.3 A, lever-type fuse terminal block
for 5 x 20 mm cartridge fuses